Trouble Shooting

Afore released | 2018-08-16 09:19:30 | Click: times

Trouble Shooting

In most situations, the inverter requires very little service. However, if inverter is not able to work perfectly, we recommend the following solutions for quick troubleshooting.
 
Anyhome Series
Error display Possible causes Corresponding measures
GFCI Device Fault Leakage current sensor fault Please contact with local dealer if error remains the same after several reset.
Bus High Fault 1.AC side incorrect wiring
2.Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.Please contact with local dealer if error remains the same after several reset.
No Utility 1.AC side incorrect wiring
2.Trip, switching capacity on grid-side is too small3、Electricity grid abnormal
4.Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.Replace switch;
3.After electricity grid returns to normal, the machine will automatically restart;
4.Please contact with local dealer if error remains the same after several reset.
Ground Current Fault 1.PV(+) or PV(-)  earthing
2.Machine failure
1.Check PV(+) and PV(-) ground impedance,make sure  impedance is more than 2MΩ;
2.Please contact with local dealer if error remains the same after several reset.
Bus Fault AC side incorrect wiring
Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug to rule out bad contact.
2.Please contact with local dealer if error remains the same after several reset.
Over Current 1.AC side incorrect wiring
2.Electricity grid abnormal
3.Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.After electricity grid returns to normal, the machine will automatically restart;
3.Please contact with local dealer if error remains the same after several reset.
Over Temperature Fault 1.The machine is exposed to sun.
2.the ambient temperature is too high
 
3、Machine failure
1. Lower machine surrounding temperature or move it to a lower temperature place.
2.Please contact with local dealer if error remains the same after several reset.
PV Over Fault 1.Start-up voltage of panels is too high
2.Machine failure
1. Adjust the panel configuration to lower the input voltage.
2.Please contact with local dealer if error remains the same after several reset.
M Grid Volt Fault 1.AC side incorrect wiring
2.Electricity grid abnormal
3.Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.After electricity grid returns to normal, the machine will automatically restart;
3.Please contact with local dealer if error remains the same after several reset.
Isolation Fault 1.PV(+) or PV(-)  earthing
2.Lightening
3.Machine failure
1..Check PV(+) and PV(-) ground impedance,make sure  impedance is more than 2MΩ;
2.Please contact with after-sales if error remains the same after several reset.
Current DC Offset 1.AC side incorrect wiring
2.Electricity grid abnormal
3.Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.After electricity grid returns to normal, the machine will automatically restart;
3.Please contact with local dealer if error remains the same after several reset.
ENS Grid F Fault 1.AC side incorrect wiring
2.Grid frequency abnormal
3.Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.After electricity grid returns to normal, the machine will automatically restart;
3.Please contact with local dealer if error remains the same after several reset.
ENS Grid V Fault 1.AC side incorrect wiring
2.Grid voltage abnormal
3.Machine failure
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.After electricity grid returns to normal, the machine will automatically restart;
3.Please contact with local dealer if error remains the same after several reset.
Relay 1/2 Fault 1.Machine failure 1.Please contact with local dealer if error remains the same after several reset.
M Grid Freq Fault 1.Electricity grid fluctuations
2.Electricity grid Frequency out of range
3.Machine failure
1.After electricity grid returns to normal, the machine will automatically restart;
2.Please contact with local dealer if error remains the same after several reset.
Manual reset: disconnect the input/output switch in turn, wait until the display and LED do not light up, then turn on and off input/output switch.
 
 
 
 
 
 
Anybuild Series
Error display  Possible causes Corresponding measures
EepromErr 1.Unstable PV input voltage 
2.Machine failure
1.After PV input voltage is stabilized, the machine willautomatically restart.
2. Please contact with local dealer if error remains the same after several reset.
GFCI.Err 1.PV(+) or PV(-)  earthing
2.Machine failure
1.Check PV(+) and PV(-)ground impedance, make sure impedance is more than 2MΩ.
2.Please contact with local dealer if error remains the same after several reset.
GridF.OutLim Electricity grid fluctuations
Electricity  grid Frequency out of range
Machine failure
1. After electricity grid returns to normal,the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
GridV.OutLim 1. Off Phase
2.Electricity grid Phase/line voltage overload
3.electricity grid Voltage unbalance
1.Disconnect the input/output switch, check the AC-side wiring and reset the plug  to rule out bad contact.
2.After electricity grid returns to normal, the machine will automatically restart.
3.Please contact with local dealer if error remains the same after several reset.
IntFaultA Machine failure Please contact with local dealer if error remains the same after several reset.
IntFaultB 1.PV input voltage is too high
2.Electricity grid abnormal
3.Bus hardware overvoltage fault
1.Adjust the panel configuration to lower the input voltage.
2.After electricity grid returns to normal, the machine will automatically restart.
3.Please contact with local dealer if error remains the same after several reset.
IntFaultC Electricity grid abnormal
Unbalanced current  fault
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntFaultD 1.Electricity grid abnormal
2.Software over current fault
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntFaultE 1.Electricity grid abnormal
2.Hardware over current fault
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntFaultG 1.Electricity grid abnormal
2.DCI too high
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntFaultJ Relay failure Please contact with local dealer if error remains the same after several reset.
IntFaultK 1.Electricity grid abnormal
2.Bus differential fault
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntFaultL 1.Electricity grid abnormal
2.Low Bus voltage fault
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntFaultM 1.Electricity grid abnormal
2.High Bus voltage fault
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntFaultN Internal hardware fault Please contact with local dealer if error remains the same after several reset.
IntProtectA Offset current protection Please contact with local dealer if error remains the same after several reset.
IntProtectB Relay protection Please contact with local dealer if error remains the same after several reset.
IntProtectC Over current protection Please contact with local dealer if error remains the same after several reset.
IntProtectD 1.PV side high current
2.Boost over current protection
1.Adjust the panel configuration to lower the input current.
2.Please contact with local dealer if error remains the same after several reset.
IntProtectE 1.Electricity grid abnormal
2.Soft start overtime protection
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntProtectF When direct current is at low voltage, Soft start overtime protection Please contact with local dealer if error remains the same after several reset.
IntProtectG Bus voltage differential protection Please contact with local dealer if error remains the same after several reset.
IntProtectH Low Bus voltage protection Please contact with local dealer if error remains the same after several reset.
IntProtectI High Bus voltage protection Please contact with local dealer if error remains the same after several reset.
IntProtectJ Inverter bridge protection Please contact with local dealer if error remains the same after several reset.
IntProtectK Bus hardware overvoltage protection Please contact with local dealer if error remains the same after several reset.
IntProtectL Power module protection Please contact with local dealer if error remains the same after several reset.
IntProtectM 1.electricity grid unbalance
2.Unbalanced current protection
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntProtectN 1.Electricity grid abnormal
2.Hardware overcurrentprotection
1.After electricity grid returns to normal, the machine will automatically restart.
2.Please contact with local dealer if error remains the same after several reset.
IntProtectO MCU protection Please contact with local dealer if error remains the same after several reset.
IntProtectP Frequency fault protection Reset grid frequency in accordance to local grid standard
IntProtectQ DCI too high protection Please contact with local dealer if error remains the same after several reset.
IntProtectR DCI  offset  protection Please contact with local dealer if error remains the same after several reset.
IntProtectS Voltage offset protection Please contact with local dealer if error remains the same after several reset.
IntProtectT PV  over current protection Please contact with local dealer if error remains the same after several reset.
IntProtectU Internal hardware abnormal protection Please contact with local dealer if error remains the same after several reset.
IsolationErr 1.PV(+) or PV(-)  earthing
2.Lightening
3.Machine failure
1.Check PV(+) and PV(-) ground impedance, make sure  impedance is more than 2MΩ.
2.Please contact with after-sales if error remains the same after several reset.
PV.Reverse 1.PV polarity reverse protection
2.Machine failure
1.Turn off input/output switch,check if pv polarity is correct or not, for troubleshooting.
2.Please contact with after-sales if error remains the same after several reset.
PVVoltOver PV The input voltage is too high 1. Adjust the panel configuration to lower the input voltage.
2.Please contact with local dealer if error remains the same after several reset.
SPICommErr SPI communication error Please contact with local dealer if error remains the same after several reset.
TempOver 1.The machine is exposed to sun.
2.the ambient temperature is too high
3. The heat sink or fan blocked by foreign matter
4.Machine failure
1. Lower machine surrounding temperature or move it to a lower temperature place.
2. Remove foreign matter.
3.Please contact with local dealer if error remains the same after several reset.
TempSensorErr Abnormal temperature sensor Please contact with local dealer if error remains the same after several reset.
ExtFanErr 1.Fan blocked by foreign matter
2.Machine failure
1.Remove foreign matter.
2.Please contact with local dealer if error remains the same after several reset.
IntFanErr Internal fan fault Please contact with after-sales if error remains the same after several reset.
 
 
l Restart: Disconnect input and output switches in order, reconnect them after LCD and indicating lights go off.
l If there is no display on the LCD, please check both AC and DC wiring.
l If the input DC voltage is higher than start up voltage, the inverter still doesn’t work, please call local service.
l If it is intended to replace the cable or open the enclosure lid, please call our service.
l Under the low light conditions, the inverter may continuously start up and shut down. It is due to insufficient power generated to operate the control circuits.